The CHFS series cut-off valve is a self-operated emergency safety shut-off valve and serves as a critical safety protection device in gas transmission and distribution systems. It features optional ultra-high (or ultra-low) pressure cut-off functionality, enabling it to rapidly interrupt gas flow when system pressure reaches the preset warning threshold, thereby safeguarding downstream systems. It is especially suitable for medium-to-high pressure applications.
Technical Specifications
Maximum allowable inlet pressure Pe, max: ≤ 100 bar
Inlet pressure range bpe: 0.1–100 bar
Cut-off pressure range Wh: 0.1–80 bar (40 bar)
Cut-off accuracy class AQ: ≤ 2.5
Response time ta: ≤ 1 sec
Operating temperature −20 °C to 60 °C
Flow coefficient Cg: ≤ 18300
Connection size (flange) DN50~DN150 (PN40 or Class 600)