最后更新: 2023-07-07
Cut-off valve-J_0

#10189 Gas shut-off valve

Cut-off valve-J

RQJ/*/10F-CHFS系列

标签

CHFS series shut-off valve is a self-operated emergency safety shut-off valve, which is an important safety protection device in the gas transmission and distribution system. Its ultra-high (ultra-low optional) pressure cut-off function, can quickly cut off the gas flow when the system pressure reaches the warning value, to protect the safety of the downstream system. Especially suitable for high and medium pressure systems.

Technical parameters

Maximum permissible inlet pressure Pe, max: ≤ 100 bar

Inlet pressure range bpe: 0. 1-100bar

Cut-off pressure range Wh: 0.1-80bar (40bar )

Cut-off accuracy class AQ: ≤ 2. 5

Response time ta: ≤ 1sec & nbsp;

Operating temperature -20℃~60℃

Flow coefficient Cg: ≤ 18300

Connection size (flange) DN50~DN150 (PN40 or Class600)

联系我们了解更多产品信息